New method for measuring ice build up on heat pumps The use of heat pumps has increased along with the green transition to environmentally friendly forms of energy. Many large air to water heat pumps are already installed where the energy in the air is used to evaporate a refrigerant either directly where the refrigerant is present in the evaporator or indirectly where a frost-proof one circulates brine.

WRITTEN BY Michael Elstrøm

Icicles Storage

With both types, you are challenged by ice build-up when the outdoor temperature is lower than+ 8 C. This is due to the temperature difference between the air and the coolant/brine. Another factor is the weather, where humidity, rain, and wind also play a role in the build-up of ice.

Ice build-up affects the efficiency of the evaporator, therefore it is important to be able to measure the formation of ice and control the defrost in accordance with the conditions. 

There are several methods for monitoring ice formation, most are indirect and in many cases are not always entirely accurate. Temperature difference control is widely used, in this way you measure the input and output temperature on coolant/brine. 

Here it is assumed that when the temperature difference is approx. halved compared to the evaporator, defrost is then initiated.

HB Products has optimized its HBDF defrost sensor which has been developed for Defrost on Demand for cold storage so now it can also control defrosting on the air evaporator and cold storage/production areas with an air temperature of approx.+1 to+ l0°C (wet ice). The sensor consists of a thin insulated wire which is mounted or directly wound on the evaporator tubes located between the aluminum fins. 

The measuring principle is capacitive and when the air surrounding the wire partially turns to ice, the measuring signal will increase, thereby you can start defrosting with an ice build-up from 1 to 2mm ensuring higher efficiency. 

Advantages: Direct measurement is made possible independent of the operating conditions of the heat.

Download The PDF Article: 

Automatic Defrost Best Practice for Effective Defrost ( pdf, 1.58 MB )

relate

The Myth Regarding the Use of Ammonia in a DX Designed refrigeration system

The Myth Regarding the Use of Ammonia in a DX Designed refrigeration system

The Myth Regarding the Use of Ammonia in a DX Designed refrigeration systemThe desire to use the wor...

White Paper : Vapor Quality Sensors [Before 2022]

White Paper : Vapor Quality Sensors [Before 2022]

Reduction of energy consumption using vapor quality control ( pdf, 2.53 MB )  ...

White Paper : Vapor Quality Sensors 2023

White Paper : Vapor Quality Sensors 2023

Energy Efficient Pump Systems - Circulation Rate Control ( pdf, 3.62 MB )       ...

Leakage Detection - Detecting CO2 Leakage Into Ammonia

Leakage Detection - Detecting CO2 Leakage Into Ammonia

Two different sensors are available for detecting leakage in CO2/ammonia cascade systems and they bo...

Detection of ammonia leakage into brine

Detection of ammonia leakage into brine

How to use a pH sensor for detection of ammonia leakage into brine ?When ammonia leak into brine the...

Comment

Anonymous

◎Welcome to in the discussion,Please express your views and opinions.