HBProducts | Vapor Quality Sensors | Compressor Protection-Rod Style
Technical data: HBCP
HBCP is a simplified variant of the HBX vapor quality sensor used at the compressor inlet. HBCP can provide an alarm, when the liquid content in the gas exceeds the critical set point. This alarm and a measured value are typically sent to a PLC. This information can be used for controlling the system and stop the compressor to avoid liquid slugging.
The sensor can prevent liquid refrigerant from entering the compressor and causing damage and break down. Especially in larger systems with several evaporators it can be difficult to control all unit and this sensor can be used for both surveillance and trouble shooting.
The HBCP and the vapor quality sensor measures the amount of liquid in the gas passing through the sensor and react instantly. The sensor is available in two versions:
- Rod style sensor which must be installed in an elbow after at the end of a horizontal pipe. The sensor must be located at the bottom of the pipe where the liquid flows. The sensor will not work if located at the middle of the pipe or in a vertical pipe.
- The strainer house sensor is installed in an empty strainer house, and it measures all the liquid flowing on the walls.
The rod style version is available in two lengths 150 and 300 mm suitable for different pipe sizes. The longest version is typically needed for pipes larger than 2”
Product features
- The sensor protects the compressor against damage in the event of liquid hammer from the system.
- Setting up the sensor using a PC allows for adjustments to match the system and the compressor.
- Split design which makes it easy to install and perform diagnostics on.
- Instantaneous reaction without delays.
Applications

Connection Diagram

HBCP-ROD Style
Power supply | Mechanical specifications | ||
Voltage | 24 V AC/DC + 10% | Thread connection | 3/4” & 1" NPT / BSPP |
Current consumption - sensor only* | 600 mA | Material - mechanical parts | AISI 304 / PTEE |
Plug connection | M12, 5 pins - DIM 0627 | Material - electronic parts | Nylon 6 (PA) |
Output | Dimensions | See drawing | |
Output type | PNP-1 A | Cable | |
Output function | NC or NO | Cable size | 5 m - 3 x0.25 mm2 |
Environmental conditions | Cable glands | PG7 / M8 | |
Ambient temperature | -30°C...+50°C | Cable resistance | 500 Ohm/Km |
Max. pressure | 100 bar | Indication | |
Waterproof rating | IP65 | LED Indication | Green, yellow, and red
|
Vibrations | IEC 60068-2-6 (4g) | Configurations | |
Approvals | Type of configuration | With the HB Tool | |
CE | EN 61000-2 | Tool to be used | HBCP or HBX software
|
Order Code
Pipe size (compressor line) | Length | Connection | Ordering code |
---|---|---|---|
2" | 150 mm | 3/4" NPT | HBCP-1.5-2 |
2" | 150 mm | 3/4" BSPP | HBCP-1.5-6 |
> 2" | 300 mm | 3/4" NPT | HBCP-3-2 |
> 2" | 300 mm | 3/4" BSPP | HBCP-3-6 |
> 2" | 300 mm | 1" BSPP | HBCP-3-8 |
> 2" | 300 mm | 1" NPT | HBCP-3-9 |
Electronic Part | Must be calibrated on-site | HBCP-EL |